Load-break switch
Module for switching feeders and distribution circuits.
Compact, modular ring main unit for secondary distribution, control, and protection in medium-voltage networks.
Gas Insulated Ring Main UnitMGC 24/36 integrates switching, protection, and isolation functions into a gas-insulated ring main unit platform.
Its architecture supports load-break switch, vacuum circuit breaker, and switch-fuse modules. Basic units can be combined in a common tank to meet customized network configurations.
Functions are combined according to the project's diagram and protection strategy.

Module for switching feeders and distribution circuits.
Protection module with short-circuit breaking capability.
Compact transformer protection using high-voltage fuses.
Isolation and connection functions for busbar configurations.
Module adaptable to incoming feeders, outgoing feeders, and specific needs.
Configuration for potential transformers and metering functions.

Main components remain inside a tank with a high level of environmental protection.
AFLR classification available for front, lateral, and rear protection during internal arc events.
Design with a specified annual gas leakage rate of ≤0.01%.
Up to 10,000 operations for selected functions and an IK10-rated enclosure.
Reference ratings for load-break switch, vacuum circuit breaker, and fuse modules.
| Parameter | MGC 24 kV | MGC 36 kV |
|---|---|---|
| Rated frequency | 60 Hz | 60 Hz |
| Rated current | 630 A | 630 A |
| Power-frequency withstand voltage | 65 / 79 kV | 95 / 118 kV |
| Lightning impulse | 125 / 145 kV | 185 / 215 kV |
| Rated short-time withstand current | 20–25 kA / 4 s | 25 kA / 3 s |
| Rated peak withstand current | 50 / 63 kA | 63 kA |
| Gas pressure at 20 °C | 0.04 MPa | 0.04 MPa |
| Annual leakage rate | ≤0.01% | ≤0.01% |
| Tank protection | IP67 | IP67 |
| Enclosure protection | IP41 / IK10 | IP4X / IK10 |
Basic modules can be combined on request in a common tank for compact, customized solutions.
The supplied reference lists a depth of 750 mm for 12 kV switchgear and a height of 1,450 mm without the low-voltage compartment. Optional low-voltage compartment heights are 200, 360, and 470 mm.
| Number of modules in common tank | 1 | 2 | 3 | 4 | 5 | 6 |
|---|---|---|---|---|---|---|
| Net tank width (mm) | 325 | 65* | 975 | 1,300 | 1,625 | 1,950 |
Share the required functions, voltage, current, protection, and layout to define your MGC 24/36 configuration.