IP67 gas tank
Medium-voltage components remain protected from dust and moisture in a sealed compartment.
Compact, modular cubicle-type switchgear for primary distribution with demanding continuity and safety requirements.
Cubicle Type Gas Insulated SwitchgearMGX-36 combines SF₆ gas insulation, modular construction, and a cubicle-type enclosure for networks up to 40.5 kV.
The platform covers rated currents of 1,250, 2,500, and 3,150 A, with functions for incoming and outgoing feeders, metering, bus ties, and sectionalizing. It is designed for applications where availability and efficient use of space are critical.

Medium-voltage components remain protected from dust and moisture in a sealed compartment.
31.5 kA AFLR design for 1 second, providing front, lateral, and rear protection.
20,000 circuit breaker operations; 10,000 for 3,150 A. Disconnectors and grounding devices support 5,000 operations, according to the brochure.
Rated filling pressure of 0.02 MPa at 20 °C and a specified annual leakage rate of ≤0.01%.
Values from the MGX-36 v2 brochure's technical table. Final selection depends on the project configuration.
| Parameter | Value |
|---|---|
| Rated voltage | 40.5 kV |
| Rated frequency | 60 Hz |
| Rated current | 1,250 / 2,500 / 3,150 A |
| Power-frequency withstand voltage, 1 min: phase-to-phase and phase-to-ground | 95 kV |
| Power-frequency withstand voltage, 1 min: isolating distance | 118 kV |
| Auxiliary and control circuit withstand voltage | 2 kV |
| Lightning impulse: phase-to-phase and phase-to-ground | 185 kV |
| Lightning impulse: isolating distance | 215 kV |
| Rated short-time withstand current | 25 / 31.5 kA, 4 s |
| Rated peak withstand current | 63 / 80 kA |
| Short-circuit current Isc* | 25 / 31.5 kA · function to be confirmed |
| Short-circuit making current | 63 / 80 kA |
| Circuit breaker electrical endurance | 30 operations |
| Rated operating sequence | O–0.3 s–CO–180 s–CO |
| Circuit breaker mechanical endurance | 20,000 operations · 10,000 for 3,150 A |
| Disconnector / grounding switch endurance | 5,000 operations |
| Circuit resistance | ≤ 120 μΩ (1,250 A) · ≤ 80 μΩ (2,500 A) · ≤ 50 μΩ (3,150 A) |
| Rated gas pressure at 20 °C | 0.02 MPa |
| Annual leakage rate | ≤ 0.01% |
| Insulating gas | SF₆ |
| Compartment protection | IP2XC |
| Tank protection | IP67 |
| Enclosure protection | IP41 · IK10 |
| Internal arc classification | AFLR 31.5 kA / 1 s |
* The brochure labels both 25 / 31.5 kA (Isc) and 63 / 80 kA as “short-circuit making current.” Confirm the function corresponding to Isc with Nexgrid before selecting the equipment.

Main panel for power supply or distribution to load circuits.
Overhead incoming configuration listed as “Overhead Incoming” in the brochure.
Incoming feeder function with an integrated voltage transformer.
Busbar sectionalizing with a power circuit breaker.
Busbar connection configuration with an isolation function.
Panel dedicated to voltage metering and protection signals.
The switchgear can be bolted or welded to the foundation channel. Channel flatness must be controlled to ensure alignment, operation, and proper load distribution.
| Panel width L | Anchoring dimension L1 |
|---|---|
| 600 mm | 430 mm |
| 800 mm | 630 mm |
| 1,000 mm | 830 mm |
The dimension table assigns 600 mm to 1,250 A and 1,000 mm to 3,150 A. For 2,500 A it prints “65 mm,” while the anchoring table includes a width of 800 mm. Confirm the width of the 2,500 A version with Nexgrid.
IEC 62271-1 · common specifications.
IEC 62271-100 · alternating-current circuit breakers.
IEC 62271-102 · disconnectors and grounding switches.
IEC 62271-103 · switches above 1 kV and up to 52 kV.
IEC 62271-105 · switch-fuse combinations.
IEC 62271-200:2011 · metal-enclosed switchgear.
IEC 60044-2 · inductive voltage transformers.
IEC 60044-1 · current transformers.
Share your diagram, rated current, short-circuit level, and required functions to define your C-GIS configuration.